ORP Analyzer MRP 66

This analyzer can measure ORP simultaneously from two sensors or it can measure ORP and pH. Two temperature measurements can be added. Sensors can be installed at one point or at different points up to 1,000-m distance from analyzer.

The analyzer can produce an arithmetical average of both measurements. The arithmetical average is converted to current signal to the third output and can be used as an input value of controller.

The analyzer contains one or two PID Controllers with width or frequency pulse output. Output can be unidirectional for solenoid valves or dosing pump control, and bi-directional for control drives with continuous movement. The analyzer can be also supplied with closed loop control 0(4) - 20 mA.

The analyzer is supplied in version T for indoor installation and in version V for outdoor installation.

Analyzer Specifications
Measurement Range ORP -1000mV to +1000mV
pH 0,00 to 14,00
Temperature -5 to 105°C
Sub Ranges (Analogue Output) ORP ±1000mV,±500mV,±200mV, or other
pH
0,0 - 14,0; 0,0 - 10,0
2,0 - 12,0 4,0 - 14,0
2,0 - 7,0 4,0 - 9,0
7,0 - 12,0 or other
Temperature 0 to 50°C, 0 to 100°C, or other
Display 2-line alphanumeric LCD readout
16 digits per line
Output 1 up to 4 outputs 0(4) ... 20 mA
Load max. 500 Ohm
Temperature Compensation -pH automatic in range -5 to 105°C
Basic Accuracy - ORP ± 0,5% of the range
Basic Accuracy - pH ± 0,5% of the range
Basic Accuracy - Temperature ± 0,3°C
Relay Outputs none, 2 or 4 relays (high/low)
(set points, hysteresis, delay - programmable)
voltage free contact, 250 V/50 Hz - max. 3 A
24 Vss - max. 0,5 A
Time Delay 0,1 to 240 minutes
Controller 2x single-parameter PID controller with
analogue or pulse output
Voltage Protection built-in lightning protection circuitry
Automatic Sensor Cleaning adjustable frequency in range
of 1 minutes to 24 hours
Enclosure IP 65
Power max. 20 VA
Dimension W 219 x H 184 x D 115 mm
Weight cca 1,5 kg
Ambient Conditions
Temperature 0 to +35°C/-20 to +35°C - version T/version V
Barometric Pressure 600 to 1060 hPa
Relative Humidity 10 ... 90%

* Valid for resistance load