Je nutné si stáhnout novou verzi flash přehrávače!

Conductivity controller MFD 88 - conductivity

Up to 12 measurement channels simultaneously

Up to 8 output relays

RS 485 MODBUS, WIFI




The MFD 88 – conductivity controller is a twelve channel instrument, which can measure conductivity and temperature in twelve channels simultaneously. Sensors can be at different points, at a distance of up to 500 m from the controller.

All constants specific to the particular place of measurement, (e.g. calibration constants) are stored in sensors or input blocks, so it is possible change of installation place without necessity of recalibration.

Interconnection between controllers and sensor is always accomplished by ordinary non-shielded two wire cable even in case of application with automatic mechanical cleaning.

Interface of instruments comprise: Serial RS 485 Modbus (RTU + ASCII ), WIFI for easy communication with notebooks, tablets, mobiles.

The controller is provided with four analogue active current outputs. The outputs can be configured as two state also and in this mode can operate as four more relays. The total number of relays is possible increase in this way to eight.

Four programmable relay outputs can be used for signaling of exceeding of adjusted limit values or as power contacts for controlling solenoid valves, actuators or contactors in the process.

Temperature range is expanded to – 20 to 50°C

Supply voltage can be 230V, 110V 50/60Hz and 24V=

The controller is manufactured in version T - for indoor installation and in version V - for outdoor installation.

The controller can convert measured conductivity to conductivity that should be measured at a temperature of 25 °C. The temperature dependence constant can be set or also obtained from measurement at 2 different temperatures. The controller calculates the constant than.

Specifications
Measurement Range (display) Conductivity 0,2 to 200 000 µS/cm, with automatic switching over
Temperature 0 až 100°C
Sub Ranges (Analogue Output) - Conductivity 5, 10, 20, 50, 100, 200, 500 µS/cm
1, 2, 5, 10, 20, 50, 100, 200 mS/cm, or other
Display backlighted graphic display
Outputs active 2 or 4 outputs 0(4) - 20 mA
Load max. 500 ohm
Temperature Compensation automatic in range 1 to 100°C
Coefficient of Temperature Dependence 0 to 5%/°C
Basic Accuracy - Conductivity ±1% of the range
Basic Accuracy - Temperature ±0,2°C
Relay Outputs none, 2 or 4 relays
(set points, hysteresis, delay - programmable)
voltage free contact, 250 V/50 Hz - max. 3 A
*24 Vss - max. 0,5 A
Time Delay 0,0 to 240 minutes
Controller 2x single-parameter PID controller with analogue or pulse output
Voltage Protection built-in lightning protection circuitry
Enclosure IP 65
Supply Voltage 230 V +6% -15%, 50/60 Hz, 24V= ±20%
Power max. 20 VA
Dimensions 219x184x115 mm W x H x D
Weight cca 1,5 kg
Ambient Conditions
Temperature -20 až +50°C
input unit -20 to +70°C
Barometric Pressure 600 to 1060 hPa
Relative Humidity 10 ... 90%

* Valid for resistance load



eBRÁNA webarchitect